HTAG 50 -765 kV voltage detector

STANDARD(S) : IEC 61243-1 (2009) VOLTAGE DETECTORS CAPACITIVE TYPE TO BE USED FOR VOLTAGES EXCEEDING 1 kV A.C. CE: Compliance with European directives.

USE : These voltage detectors are designed for making sure that nominal voltage is indeed absent in a circuit in an HV system between 50 kV and 765 kV (no-voltage verification):
• The device must detect any nominal voltage in a system or station.
• It makes it possible to avoid detecting induced voltages in order to allow earthing operations.

SPECIFICATIONS :
AC voltage range possible choice from 50 to 765 kV Network frequency: 50 or 60 Hz (to be specified with the order)
• Permanent standby status with automatic wake-up function
• The presence of voltage within the calibrated range or above makes a RED indicator light up, and an audio signal is generated.
• Self-test OK: the OK status (ready for use) of the device is indicated by a GREEN indicator lamp.
• The self-test checks all the circuits, the reference detection level and the cell voltage.
• The self-test is repeated automatically throughout the ready for use state as indicated by the green indicator lamp (for 1.5 minutes).
• The battery low level is indicated by a dedicated ORANGE LED indicator going on.
• Designed for outdoor use
• Operating temperature: -25 °C to +55 °C
• Humidity: 96 % max.
• Power supply voltage: 9 V alkaline cell – IEC 6LR61
• Accepts the use of accumulators with identical supply voltage
• Yellow or red polycarbonate housing
• Dimensions: Ø 80 mm, L = 225 mm without the electrode
• Net weight: 0.618 kg with stick end fitting, without electrode
• Operating manual with a choice of languages, depending on the package.
• Package with three electrodes : 2 hooks: Ø 60 mm (AC 60) and Ø 120 mm (AC 120) and 1 straight electrode (D 100).

ADVANTAGES :
Optimised indication that can be understood clearly in all working conditions:
• The indicator light is visible in all usual workingenvironments, in sunlight or fog, with a wide visibilityangle.
• The 100 dB sound signal (from 1 metre) remainsaudible even over the noise of traffic or strong wind, thanks to natural conduction by an acoustic “horn”.

Direct access to the cell and sealed electronicscompartment. When the cell is replaced, this designprevents the following:
• accidental interchange of housing or circuitry;
• damage to electronic circuits;
• entry of humidity into the device when the cell ischanged outdoors.

HTAG063090F5C = Voltage range: 63-90 kV , Frequency: 50 Hz , Housing colour: Yellow , End fitting: Universal (U) , Contact electrode: AC60 / AC120 / D100 , Packaging: Metallic case
HTAG063090F5 = Voltage range: 63-90 kV , Frequency: 50 Hz , Housing colour: Yellow , End fitting: Universal (U) , Contact electrode: AC60 / AC120 / D100 , Packaging: Without
HTAG150150F5C = Voltage range: 150 kV , Frequency: 50 Hz , Housing colour: Red , End fitting: Universal (U) , Contact electrode: AC60 / AC120 / D100 , Packaging: Metallic case
HTAG150150F5 = Voltage range: 150 kV , Frequency: 50 Hz , Housing colour: Red , End fitting: Universal (U) , Contact electrode: AC60 / AC120 / D100 , Packaging: Without
HTAG225400F5C = Voltage range: 220-400 kV , Frequency: 50 Hz , Housing colour: Red , End fitting: Universal (U) , Contact electrode: AC60 / AC120 / D100 , Packaging: Metallic case
HTAG225400F5 = Voltage range: 220-400 kV , Frequency: 50 Hz , Housing colour: Red , End fitting: Universal (U) , Contact electrode: AC60 / AC120 / D100 , Packaging: Without

0.00 € 0.0 EUR 0.00 €

1.00 Lek


  • Voltage

This combination does not exist.

Add to Cart Buy Now

PENTA ESP (Electrical Safety Products)
PENTA ESP (Electrical Safety Products)

We are PENTA 🚀 👷🏽‍♀️ Multinational industrial leader, pioneer and expert manufacturer of electrical safety solutions, committed to ensuring your safety at every intervention! 🤝 We are the essential partner for linemen, maintenance technicians and electricians working on power generation, transmission and distribution networks all over the world, and in 9 other areas of activity. With over 1200 employees in 18 subsidiaries worldwide, PENTA adapts its products to all electrical standards and regulations of each country. You will find our electrical safety solutions under different brands.


Best Value 
Fast Delivery
Quality Consistency

Share this product:
Voltage Voltage range: 63-90 kV , Frequency: 50 Hz , Housing colour: Yellow , End fitting: Universal (U) , Contact electrode: AC60 / AC120 / D100 , Packaging: Metallic case or Voltage range: 63-90 kV , Frequency: 50 Hz , Housing colour: Yellow , End fitting: Universal (U) , Contact electrode: AC60 / AC120 / D100 , Packaging: Without or Voltage range: 150 kV , Frequency: 50 Hz , Housing colour: Red , End fitting: Universal (U) , Contact electrode: AC60 / AC120 / D100 , Packaging: Metallic case or Voltage range: 150 kV , Frequency: 50 Hz , Housing colour: Red , End fitting: Universal (U) , Contact electrode: AC60 / AC120 / D100 , Packaging: Without or Voltage range: 220-400 kV , Frequency: 50 Hz , Housing colour: Red , End fitting: Universal (U) , Contact electrode: AC60 / AC120 / D100 , Packaging: Metallic case or Voltage range: 220-400 kV , Frequency: 50 Hz , Housing colour: Red , End fitting: Universal (U) , Contact electrode: AC60 / AC120 / D100 , Packaging: Without
This is a preview of the recently viewed products by the user.
Once the user has seen at least one product this snippet will be visible.
Recently viewed Products